ATTENTION APC UPS USERS! (could apply to other UPS batteries!)

I thought it was only responsible of me to follow up on this question after REAL EXPERIENCE which could have been FATAL!

This question is right on topic with a recent event this week, where I've spent the night in hospital!.

Red Light on Smart UPS 2200

After suffering the effects of Respiratory irritation caused by inhaling toxic gases in the datacentre.

One or Two APC 3000 UPS failed in the datacentre, with battery faults, the gas possible Hydrogen Sulphide (H2S) filled the closed datacentre with possibly Hydrogen Sulphide (H2S).

I only open the door, and walked in for exposure for what could have been more than 10 seconds, it was enough to overwhelm me causing headache for the rest of the afternoon, nausea, coughing and later breathlessness after advice from "NHS 111 Online" I went to Accident and Emergency, where they wired me up to ECG, Heart Rate, Blood Pressure monitors, took blood samples every hour for testing, and oxygen and nebuliser.

I was discharged after 12 hours, being advised to rest, take it easy and the exposure and irritation should get better over 48 hours.

I'm still feeling tired, cough is getting better, but still my chest still feels very heavy which I'm told is the inflammation of the lungs,

My recommendation should you have a battery light is to isolate from the Power Supply Immediately.

e.g. turn off and discard the unit. open all windows, and vent the building, or call the Fire Services for advice, do not enter the building. H2S is toxic!

Furhter info here on H2S

https://en.wikipedia.org/wiki/Hydrogen_sulfide

http://njnnetwork.com/2010/03/your-ups-battery-backu-may-be-killing-you/


3
LVL 23

Comment

by:David Atkin
Wow, hope you're feeling better shortly Andrew.  Good of you to warn others.
1
LVL 147
Thanks, a bit tired, coughing still, and a heavy chest, caused by lung inflammation.

Ticking timebombs.... replace UPS when out of warranty, or replace batteries if you know the UPS charging circuits are working correctly. However APC will be quick to sell you a replacement battery pack, but once you open the carton, they will not refund you, if it turns out your UPS has failed, and the charing circuits are not working correctly.

So to be honest with you false economy to replace batteries on a UPS, and how many organizations have budgeted for a 2-3 year replacement UPS plan!
1
LVL 79

Comment

by:☠ MASQ ☠
It's a really good point to raise. Any UPS with lead acid batteries can do this. The gas released is not only toxic by inhalation but when it hits the moisture lining the lungs turns to acid! Should be listed as a risk in any server room, as, let's be honest with AC to maintain temperatures there is little ventilation. Specialist management by fire services is needed. Use the same protocol as you had for Halon gas fire extinguishers.
0
LVL 147
H2S can also enter the blood directly via the eyes!
0
LVL 17

Comment

by:Leonidas Dosas
Has the H2S some intense odor or color to distinguish it from other odors or smokes?
0
LVL 147
at low dosage it's odourless, and people have different sensitivities...it has no colour

also can be explosive

but at high concentrations, rotten eggs, or sulphuric acid, battery acid smell
0
LVL 115

Comment

by:John
Andy - I offer you my very best wishes and I hope you have a complete recovery. Sounds nasty.  ... John
0
LVL 147
Thanks John
0